Telect 009-0004-1045 1RU -48Vdc Dual-Feed 20x20 GMT Fuse Alarm Panel. Telect’s low-cost Dual-Feed 20x20 GMT Fuse Alarm Panels are 1RU (EIA) power shelves providing protection and redundancy for -48 Vdc telecommunications equipment. Each side of 20 GMT fuses handles a combined continuous load of 50A (max,) at a max. output of 10A per position. Power-fail and fuse alarm relays provide standard, Form-C dry contacts.Telect Model Number: 009-0004-1045Specifications:Mechanical / Environmental Specifications:Dimensions (nominal without brackets)Width: 17.25 in. (438.2 mm) Height: 1.70 in. (43.2 mm) Depth: 8 in. (203.2 mm) Weight Installed: ~5 lb (~2.25 kg)Acoustic noise 0 dBA above ambient Temperature range -25°C to 60°C (-13°F to 140°F) Humidity 5% to 85% and noncondensing Compliance NEBS Certified, UL, Telcordia GR-1089-CORE & GR63-CORE Ground terminal Screws: #6-32 stud with washer and KEPS nut. KEPS nut diameter is 0.375 in. (9.6 mm) Lugs: Single compression to accommodate KEPS nut Cable: #10 - #12 AWG copper, depending on PDU circuit interrupter Torque: 8.7 in.-lb (~0.98 N•m), max.Input terminalsType: Dual-hole compression, #10 studs with washers and 10-32 KEPS nuts on .625 in. centers. Max. lug width is 0.55 in. (13.9 mm) Cable: #10 - #2 AWG copper, depending on lug and PDU circuit breaker or fuse Torque: 20 in.-lb (2.25 N•m)Output & Alarm terminals (Wire Binding Screw) Screw: #3 slotted captive screws Wire: #16 AWG (max.) bare wire; #16 - #14 AWG (max.) with lug Forked Lug: Burndy TP14-2F or TP14-2Z** Spacing: .25 in. (6.35 mm) centerline with.19 in. (4.8 mm) between barriers Torque: 3.5 in.-lb (0.39 N•m)Electrical Specifications:Operating voltages -20 to -60 VdcCurrent capacity 50A per bus (100A total)Fuse capacity 20 GMT fuses per busMaximum input interruption device rating 60A per feedMaximum output interruption device rating 10A GMT fuseMaximum continuous output load rating 7A per 10A fuse positionAlarm relay contacts 2A @ 30 Vdc, 0.6A @ 60 VdcAlarm board power rating @ 48 Vdc 1WWorst case heat dissipation @50A per bus less than 20W (68.3 Btu/hr)Percentage of full load heat dissipation at nominal voltage less than 1% of total load wattage